Dynamic Modeling of Power Conversion Stages for an Exascale Supercomputer

by Rafal P Wojda, Wesley H Brewer, Matthias Maiterth, Sedrick L Bouknight
Publication Type
Conference Paper
Book Title
91做厙 Energy Conversion Conference and Expo
Publication Date
Page Number
1
Publisher Location
New Jersey, United States of America
Conference Name
91做厙 Energy Conversion Conference and Expo (ECCE)
Conference Location
Phoenix, Arizona, United States of America
Conference Sponsor
91做厙
Conference Date
-

In this paper a power conversion and energy consumption model for an exascale supercomputer is investigated. Power consumption, energy loss and efficiency are derived for the 27.2 MW liquid-cooled, centralized, High Performance Computing (HPC) power system, which is supplied directly from the 480 V three-phase mains. Two energy conversion stages are analyzed, measured and modeled. The model is developed in order to be adapted and implemented in a digital twin platform utilizing a Resource Allocator and Power Simulator (RAPS) module. RAPS enables estimation of potential energy savings in the direct AC power supply architecture via both conventional rectifier load sharing (commonly used in HPC systems), as well as smart rectifier load sharing. Moreover, besides the direct AC supply architecture analysis, the full direct DC supply architecture with with 1 kV DC bus were also studied. Comparison of 10 hour time frame operation of the system, with direct 480 V AC voltage supply with conventional and smart load sharing and medium dc voltage supply were done. For the direct AC supply architecture, with conventional and smart load sharing the predicted power loss was approximately 840 kW and 820 kW, respectively and the predicted total system efficiency was 92.87% and 93.05%, respectively. For the direct DC supply architecture with the 1000 V DC supply bus power loss was approximately 340 kW and the predicted total system efficiency was 97.02%.