Abstract
Lately, solar photovoltaic (PV) has received significant interest due to its economic and environmental benefits. As the integration of renewable energy sources (RES) increases into existing power grids, challenges such as the decrease in short circuit ratio (SCR) are introduced. This paper investigates a case study of the Saudi power grid, examining the voltage stability as the grid transitions from traditional power generation to 100% penetration of solar PV gradually. Moreover, the paper explores the relationship between the increase in solar penetration and the potential effects on the short circuit MVA (SCMVA), which could significantly impact the overall SCR of the system. To meet the North American Electric Reliability Corporation (NERC) recommendation of maintaining SCR at a particular level, synchronous condensers (SC)s were integrated into the grid. The effectiveness of utilizing SCs to maintain the system voltage at optimal levels in a fully solar grid is also considered. In addition, this paper covers the weak grid analysis via utilizing the Newton-Raphson load flow method, along with PV and QV curve analyses. The purpose behind that is to determine weak bus locations in need of voltage improvements, and to meet the amount of reactive power to be injected. Finally, the amount of power being delivered by SCs will be added progressively in three scenarios to show the enhancements on SCR more precisely.